*Helpful Charts
Untinned copper
wires
Stranded tinned
copper wires
SWG to AWG
Conversion
American Wire Gauge
Untinned copper wires
|
| AWG standard notation |
Nominal diameter |
Cross-section area,
mm X mm |
Running weight |
Running resistance |
| mm |
inch |
g/m |
lb/1000 ft |
ohm/m |
ohm/1000 ft |
| 10 |
2.600 |
0.1024 |
5.309 |
46.77 |
31.43 |
0.0033 |
0.999 |
| 11 |
2.300 |
0.0906 |
4.155 |
37.09 |
24.92 |
0.0041 |
1.260 |
| 12 |
2.050 |
0.0807 |
3.301 |
29.42 |
19.77 |
0.0052 |
1.588 |
| 13 |
1.830 |
0.0720 |
2.630 |
23.33 |
15.68 |
0.0066 |
2.003 |
| 14 |
1.630 |
0.0642 |
2.087 |
18.50 |
12.43 |
0.0083 |
2.525 |
| 15 |
1.450 |
0.0571 |
1.651 |
14.67 |
9.858 |
0.0104 |
3.184 |
| 16 |
1.290 |
0.0508 |
1.307 |
11.63 |
7.818 |
0.0132 |
4.016 |
| 17 |
1.150 |
0.0453 |
1.039 |
9.23 |
6.200 |
0.0166 |
5.064 |
| 18 |
1.020 |
0.0402 |
0.817 |
7.32 |
4.917 |
0.0209 |
6.385 |
| 19 |
0.912 |
0.0359 |
0.653 |
5.80 |
3.899 |
0.026 |
8.051 |
| 20 |
0.813 |
0.0320 |
0.519 |
4.60 |
3.092 |
0.033 |
10.15 |
| 21 |
0.724 |
0.0285 |
0.412 |
3.65 |
2.452 |
0.042 |
12.80 |
| 22 |
0.643 |
0.0253 |
0.325 |
2.89 |
1.945 |
0.053 |
16.14 |
| 23 |
0.574 |
0.0226 |
0.259 |
2.29 |
1.542 |
0.067 |
20.36 |
| 24 |
0.511 |
0.0201 |
0.205 |
1.82 |
1.223 |
0.084 |
25.67 |
| 25 |
0.455 |
0.0179 |
0.163 |
1.44 |
0.9699 |
0.106 |
32.37 |
| 26 |
0.404 |
0.0159 |
0.128 |
1.14 |
0.7692 |
0.134 |
40.81 |
| 27 |
0.361 |
0.0142 |
0.102 |
0.908 |
0.6100 |
0.169 |
51.47 |
| 28 |
0.320 |
0.0126 |
0.080 |
0.720 |
0.4837 |
0.213 |
64.90 |
| 29 |
0.287 |
0.0113 |
0.065 |
0.571 |
0.3836 |
0.268 |
81.83 |
| 30 |
0.254 |
0.0100 |
0.051 |
0.453 |
0.3042 |
0.339 |
103.2 |
| 31 |
0.226 |
0.0089 |
0.040 |
0.359 |
0.2413 |
0.427 |
130.1 |
| 32 |
0.203 |
0.0080 |
0.032 |
0.285 |
0.1913 |
0.538 |
164.1 |
| 33 |
0.180 |
0.0071 |
0.025 |
0.226 |
0.1517 |
0.679 |
206.9 |
| 34 |
0.160 |
0.0063 |
0.020 |
0.179 |
0.1203 |
0.856 |
260.9 |
| 35 |
0.142 |
0.0056 |
0.016 |
0.142 |
0.09542 |
1.086 |
331.0 |
| 36 |
0.127 |
0.0050 |
0.013 |
0.113 |
0.07568 |
1.361 |
414.8 |
| 37 |
0.114 |
0.0045 |
0.010 |
0.091 |
0.06130 |
1.680 |
512.1 |
| 38 |
0.102 |
0.0040 |
0.008 |
0.071 |
0.04759 |
2.128 |
648.6 |
| 39 |
0.089 |
0.0035 |
0.006 |
0.056 |
0.03774 |
2.781 |
847.8 |
| 40 |
0.079 |
0.0031 |
0.005 |
0.045 |
0.02993 |
3.543 |
1080.0 |
| AWG standard notation |
mm |
inch |
Cross-section area
mm X mm |
g/m |
lb/1000 ft |
ohm/m |
ohm/1000 ft |
| Nominal diameter |
Running weight |
Running resistance |
Adjusted average wire diameter is calculated from the formula, as
follows:

|
Click here for More
Download
e-mail:
tpsbpl@yahoo.co.in

total_project_solutions@yahoo.co.in

Updated on:
Friday, 27 January 2006